Abstract
A widely embraced approach to mitigate the dynamic degradation in low-inertia power systems is to mimic generation response using grid-connected inverters to restore the stiffness of the grid. In this article, we seek to challenge this approach and advocate for a principled design based on a systematic analysis of the performance trade-offs of inverter-based frequency control. With this aim, we perform a qualitative and quantitative study comparing the effect of conventional control strategies-droop control (DC) and virtual inertia (VI)-on several performance metrics induced by L2 and L∞ signal norms. By extending a recently proposed modal decomposition method, we capture the effect of step and stochastic power disturbances, and frequency measurement noise, on the overall transient and steady-state behavior of the system. Our analysis unveils several limitations of these solutions, such as the inability of DC to improve dynamic frequency response without increasing steady-state control effort, or the large frequency variance that VI introduces in the presence of measurement noise. We further propose a novel dynam-i-c droop controller (iDroop) that overcomes the limitations of DC and VI. More precisely, we show that iDroop can be tuned to achieve high noise rejection, fast system-wide synchronization, or frequency overshoot (Nadir) elimination without affecting the steady-state control effort share, and propose a tuning recommendation that strikes a balance among these objectives. Extensive numerical experimentation shows that the proposed tuning is effective even when our proportionality assumption is not valid, and that the particular tuning used for Nadir elimination strikes a good trade-off among various performance metrics.
Original language | English |
---|---|
Article number | 9244565 |
Pages (from-to) | 3518-3533 |
Number of pages | 16 |
Journal | IEEE Transactions on Automatic Control |
Volume | 66 |
Issue number | 8 |
DOIs | |
Publication status | Published - 2021 |
Subject classification (UKÄ)
- Electrical Engineering, Electronic Engineering, Information Engineering
Free keywords
- Frequency control
- low-inertia power systems
- static and dynamic performance
Fingerprint
Dive into the research topics of 'Dynamic Droop Control in Low-Inertia Power Systems'. Together they form a unique fingerprint.Projects
- 1 Finished
-
ScalableControl: Scalable Control of Interconnected Systems
Rantzer, A. (PI), Jouini, T. (Researcher), Agner, F. (Researcher), Troeng, O. (Researcher), Kergus, P. (Researcher), Pates, R. (Researcher), Kjellqvist, O. (Researcher), Renganathan, V. (Researcher), Wu, D. (Researcher) & Lindberg, J. (Researcher)
2019/09/01 → 2024/08/31
Project: Research