Utvärdering av informationssystem för utrymning i hotellmiljö - Fältförsök med utrymningshissar

Forskningsoutput: Bok/rapportRapport

Abstract

This report summarizes unannounced evacuation experiments in a hotel building with evacuation elevators as one of the escape routes. The participants in the experiments were wearing an eye tracking device. The results of the experiments show that there is a high acceptance for using evacuation elevators as an escape route in the evaluated type of high-rise building. The results also show that most evacuees do not see the evacuation signage and when the signage is seen the information conveyed is, in most cases, not perceived. Blinking green lights can be used to improve the probability of seeing the evacuation signage. However, it is not certain that this increases the perception of the information conveyed by the signage.

Detaljer

Författare
Enheter & grupper
Externa organisationer
  • ÅF-Technology AB
Forskningsområden

Ämnesklassifikation (UKÄ) – OBLIGATORISK

  • Husbyggnad

Nyckelord

  • utrymningshissar, utformning av informationssystem, hotell, försök
Originalspråksvenska
UtgivningsortLund
FörlagLund University
Antal sidor35
StatusPublished - 2018
PublikationskategoriForskning

Publikationsserier

NamnLUTVDG/TVBB
FörlagBrandteknik, LTH, Lunds universitet
Nr.3217

Nedladdningar

Ingen tillgänglig data