Small and large scale fire experiments with electric cables under well-ventilated and vitiated conditions

Petra Andersson, Lars Rosell, Margaret Simonson, Viktor Emanuelsson

Forskningsoutput: TidskriftsbidragArtikel i vetenskaplig tidskriftPeer review

Sammanfattning

Results from a series of small scale (using the DIN 53 436 tube furnace) and large scale experiments (using the IEC 60332-3 rig) are presented for two types of power transmission cables used in buildings. The results are unique in that they catalogue the production of a wide variety of organic and inorganic species under different fire conditions. The experiments were conducted to provide input to an LCA model and the specific organic species studied in detail have been chosen based on the information required by the LCA model. During the process of this study it became apparent that information concerning quantitative organic species evolution from cable fires is lacking in the open literature. This paper aims to provide such information for two specific sets of fire conditions, i.e., a well-ventilated and a vitiated cable riser fire.

Originalspråkengelska
Sidor (från-till)247-262
Antal sidor16
TidskriftFire Technology
Volym40
Nummer3
DOI
StatusPublished - 2004 juli
Externt publiceradJa

Bibliografisk information

Funding Information:
The authors of the article would like to thank the Swedish Fire Research Board and the Swedish Business Development Agency for financial support and the industry partners for help throughout the project.

Copyright:
Copyright 2008 Elsevier B.V., All rights reserved.

Ämnesklassifikation (UKÄ)

  • Annan samhällsbyggnadsteknik

Fingeravtryck

Utforska forskningsämnen för ”Small and large scale fire experiments with electric cables under well-ventilated and vitiated conditions”. Tillsammans bildar de ett unikt fingeravtryck.

Citera det här